


There is a 3mm red LED in the sensor. The LED signalises the status of the sensor. Meaning of different LED signals:
|
LED activity
|
Meaning
|
||
| ON time | OFF Time | ||
| continuous blinking | 0.1s | 14.9s | normal sensor operation |
| continuous blinking | 0.3s | 0.7s | warm-up time after power on (results not stable) |
| on whilst zeroing key depressed | zeroing key pressed | ||
| triple blink after zeroing key released | 0.2s | 0.2s | confirmation of zeroing |
| continuously on | error (results incorrect) | ||
| continuously off | sensor off | ||
The single channel sensors are used more widely than the two channel sensors for reasons of price. They are smaller, use less energy, which is most important in battery operation, and the detectors produce stronger signals, allowing more stable results to be achieved, especially at low concentrations.
The advantage of the two-channel sensor is the long-term stability. The second channel (comparison channel) enables the sensor to compensate the following effects:
madur electronics has taken several steps to ensure a good long-term stability. These measures are especially effective with the one-channel sensors and have reached the point where they are only minimally exceeded by the two channel sensors. These are some of the measures used:
MadIR sensors are constructed as low-current, compact devices. The low current demand and hence minimal internal warming are a valuable improvement to the long-term stability. The power requirement is basically dependent on the voltage supply. The table below shows the four possibilities for the one-channel sensors. The power requirements do not include the power needed for the analogue outputs.
|
Version
|
DC supply range
|
AC supply range
|
Vout range
[max] |
Average supply current / power [max]1
|
|
Standard
|
13.5..18V
|
N/A
|
0..10V
|
45mA*VDC
|
|
Low Voltage
|
7.5..18V
|
N/A
|
0..5V
|
35mA*VDC
|
|
Extended Supply, Standard
|
13..32V
|
9..24VAC
|
0..10V
|
1W
|
|
Extended Supply, Low Voltage
|
7..32V
|
6..24VAC
|
0..5V
|
0.7W
|
MadIR 90 (A01) has two separate analogue outputs:
· Current output Iout, maximum range 0..25mA
· Voltage output Uout, maximum range (depending on power supply version): 0..5V or 0..10V
Both outputs are fully independent. User can set the minimum/maximum voltage/current using RS232 and madir PC software as well as corresponding minimum/maximum of gas concentration separately for each analogue output.
It is necessary to define a voltage range of more then 2 V and a current range of more than 4 mA to get an acceptable resolution of more than 2 % of the defined working range.
The analogue outputs operate from a 12-bit D/A converter. This allows a resolution of 4096 digits on 0 12 V for the voltage output and on 0 25 mA for the current output.
The current output can drive a maximum load of 500 ohm.
The voltage output requires a minimum load of 500 ohm.
The following settings are possible:
Setting A:
|
|
Electric signal
|
Gas concentration
|
||
|
minimum
|
maximum
|
minimum
|
maximum
|
|
|
Voltage output
|
0 V
|
2 V
|
200 ppm
|
600 ppm
|
|
Current output
|
4 mA
|
20 mA
|
0 ppm
|
2000 ppm
|

Setting B:
|
|
Electric signal
|
Gas concentration
|
||
|
minimum
|
maximum
|
minimum
|
maximum
|
|
|
Voltage output
|
4 V
|
10 V
|
400 ppm
|
1000 ppm
|
|
Current output
|
0 mA
|
20 mA
|
400 ppm
|
2000 ppm
|

Voltage output in Schmitt mode
The voltage output can also be configured as a Schmitt output (instead of the normal linear mode). The Lo and Hi voltage as well as Lo-to-Hi and Hi-to-Lo trip points are definable by user via RS232.
For example following settings are possible for the voltage output working in Schmitt mode:
Setting C:
|
|
Electric signal
|
Gas concentration
|
||
|
Lo voltage
|
Hi voltage
|
Lo-to-Hi trip point
|
Hi-to-Lo trip point
|
|
|
Voltage output
|
0 V
|
5 V
|
600 ppm
|
200 ppm
|
|
|
Electric signal
|
Gas concentration
|
||
|
minimum
|
maximum
|
minimum
|
maximum
|
|
|
Current output
|
4 mA
|
20 mA
|
200 ppm
|
800 ppm
|

Setting D (for reversed logic of Schmitt output):
|
|
Electric signal
|
Gas concentration
|
||
|
Lo voltage
|
Hi voltage
|
Lo-to-Hi trip point
|
Hi-to-Lo trip point
|
|
|
Voltage output
|
10 V
|
0 V
|
700 ppm
|
300 ppm
|
|
|
Electric signal
|
Gas concentration
|
||
|
minimum
|
maximum
|
minimum
|
maximum
|
|
|
Current output
|
4 mA
|
20 mA
|
200 ppm
|
800 ppm
|

Settings E (for no-hysteresis Schmitt output):
|
|
Electric signal | Gas concentration | ||
|
Lo voltage
|
Hi voltage
|
Lo-to-Hi trip point
|
Hi-to-Lo trip point
|
|
|
Voltage output
|
0 V
|
5 V
|
500 ppm
|
500 ppm
|
|
|
Electric signal
|
Gas concentration
|
||
|
minimum
|
maximum
|
minimum
|
maximum
|
|
|
Current output
|
4 mA
|
20 mA
|
200 ppm
|
800 ppm
|

MadIR Sensors are fitted with a RS232C serial interface as standard. This interface can be used for all communication between sensor and PC (programming the flash memory, calibration, sensor settings and reading out data).
The following options are also available:
· SPI - solely for reading out data
· I2C - can be used to drive an external 4.5 digit LCD display
The sensors are supplied complete with the software for operation and configuration.
The programme has the following functions:
· Read data from sensor.
· Processing the results:
· Calculates averages
· Stores the results continuously at a predetermined rate on the hard drive of the computer.
· One-off storage of the results shown on the screen on the hard drive.
· Zeroing of the sensor with gas.
· Setting the analogue outputs.
· Control: Shows the calibration curve and the parameters of the sensor.
· Calibration of the sensor with span gas.
For flow sensors the gas flow rate should not exceed 1.5 l/min. We recommend a flow rate of around 400 ml/min. There is no lower limit on the flow rate, but a reduced flow rate will slow the reaction of the sensor.
The calibration of a madIR sensor is carried out in the factory at ten separate points in the measuring range for methane or carbon dioxide. The user can view the calibration curve at any time using the software provided. It is also possible to recalibrate the sensor if necessary. This requires span gas of at least three different concentrations. It is, however, generally not necessary to recalibrate the sensor at any time. A zero correction may be sometimes required, and this can be carried out in four ways:
· No Zeroing - No correction is made. The sensor retains the last zero point set.
· Auto Zeroing - Every time the sensor is switched on the zero point is reset after 90 seconds.
· Manual Zeroing - There is a zero button on the sensor. When this is pressed the sensor takes this value as the new zero.
· Smart Zeroing - The sensor stores the averages for 15 minutes over a period of 14 days and takes the lowest value as being zero.
When zeroing the sensor be sure that the sensor is supplied with a gas of known concentration that can serve as a zero value. Fresh air is one example, assuming the area is relatively free of traffic!